Access Control Using Vistakey; Figure 3-30: Wiring The Alpha Pager Module - Honeywell VISTA-128BP Installation And Setup Manual

Commercial burglary partitioned security systems
Hide thumbs Also See for VISTA-128BP:
Table of Contents

Advertisement

VA8201 ALPHA PAGER MODULE
PARALLEL
OUTPUT
PARALLEL
PRINTER
GREEN
RED
BLACK

Access Control Using VistaKey

The VistaKey is a single-door access control module
that, when connected to the alarm system, provides
access control to the protected premises. The VISTA-
128BP supports up to 8 modules, the VISTA-250BP
supports up to 15 VistaKey modules (15 access points).
DO NOT USE BOTH the VistaKey and a
PassPoint Access Control System on the same
alarm panel.
The VistaKey module contains three zones.
U L
These zones should ONLY be used for access
control functions in UL installations. THESE
INPUT ZONES ARE NOT TO BE USED FOR
FIRE AND BURGLARY APPLICATIONS IN UL
INSTALLATIONS.
VistaKey Features
Each VistaKey communicates with the VISTA-
128BP/VISTA-250BP via the V-Plex polling loop.
In the event local power to the VistaKey is lost,
the VistaKey module provides backup monitoring
of the access point door via a built-in V-Plex device
that is powered solely from the polling loop. It is
programmed as a new type of V-Plex device as
part of the control's V-Plex Device Programming.
A serial number label is affixed to the VistaKey
module for manual entry of its serial number.
The VistaKey supports up to 500 cardholders.
WWW.DIYALARMFORUM.COM
DATA/
POWER
SERIAL
OUTPUT
TO PHONE
BROWN
TO LINE
6
7
23
26
AUX
AUX
TIP RING
PWR.
HANDSET
GND.
(ZONE 9)

Figure 3-30: Wiring the Alpha Pager Module

WWW.DIYALARMFORUM.COM
GREEN
RED
BLACK
ORANGE
HOME AUTOMATION COMPUTER
GRAY
PHONE
CORD
27
28
29
30
1 2 3 4 5 6 7 8 9
TIP RING
INCOMING
EARTH
GROUND
CONTROL PANEL
The addition and removal of VistaKey modules
from the system is easily accomplished via the
VISTA-128BP/VISTA-250BP keypad.
All configurable options for each VistaKey are
accomplished via software, firmware, and
nonvolatile memory, eliminating the need for PC
board jumpers. The access point zone number (1-
15) is set via a user-friendly, 16-position rotary
switch.
Each VistaKey provides one open-collector output
trigger (sink 12mA @ 12VDC).
Mounting and Wiring the VistaKey
For detailed instructions on how to install and
program the VistaKey, refer the Installation and
Setup Guide that accompanies the VistaKey-
SK.
To mount and wire the VistaKey module, perform the
following steps:
Step
Action
1
Mount the VistaKey, door strike or mag lock,
and card reader.
2
Mount the door status monitor (DSM) and/or
request-to-exit (RTE) devices.
3
Using Figure 3-31 as a reference, connect the
card reader interface cable to TB3, making
the +5V or +12V connection last.
Section 3 - Installing the Control
NOTE
WHEN USING THE VA8201, ZONE 9 CAN NO
LONGER BE USED AS A PROTECTION ZONE.
SPLICE
INCOMING TELCO LINE
TIP
RJ31X
RING
JACK
J8
BROWN WIRE
FROM 4142 TR
TRIGGER CABLE
PREMISES
CALLER ID UNIT,
ANSWERING
MACHINE, AND
PHONES
CALLER ID
UNIT
ANSWERING
MACHINE
VA8201-SOC-V1
3-25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vista-250bpVista-128sia