VISTA-128BP/VISTA-250BP Installation and Setup Guide
Installing the Audio Alarm Verification Module
Audio Alarm Verification (AAV) is not permitted
U L
in UL installations.
•
685 Receiver software must be rev. 4.6 or
higher. Earlier versions will not hold the
phone line connection.
•
Contact ID code for "Listen-in to Follow" is
606. Contact ID is the only reporting format
that will send a "Listen-in to Follow."
•
If you are also using a 4285/4286 VIP
Module, be sure to follow Figure 3-37 when
making connections.
The UVS consists of a UVCM and at least one UVST.
The UVCM board has a DC power jack and a 34-
position terminal block for making connections to a DC
power source, UVSTs, telephone lines, music source, or
to the 4286 VIP Module; and to a control panel's voice
trigger and bell outputs (if required). Refer Figure 3-
28 for wiring connections. For a detailed explanation
of the wiring connections and the functions of the DC
power jack and terminal block positions, refer to the
installation instructions that accompany the UVS.
3-30
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
If the phone plug is disconnected from the
control, the premise's phones will not operate.
NOTES:
•
When the AAV indicates that the audio alarm
verification session is completed, all keypad
sounds are restored. Sirens are restored if the
alarm timeout period has not expired.
•
As part of its fail-safe software, the control limits
all audio alarm verification sessions to 15 minutes.
This is because once the session begins, the AAV
Module controls the duration.
•
If a new Fire alarm should occur during a
session, the control breaks the phone connection
and sends the new Fire Alarm report, then re-
triggers the AAV Mode. All other dialer messages
triggered during ongoing conversation are held
until either the AAV Module signals that it is
inactive, or the 15-minute timeout occurs.