Troubleshooting
4.16 FourWay Valve Abnormality
EA
Remote
Controller
Display
Method of
The room temperature thermistor and the indoor heat exchanger thermistor are checked if they
Malfunction
function within their normal ranges in each operation mode.
Detection
Malfunction
A following condition continues over 1 ~ 10 minutes after operating for 5 ~ 10 minutes.
Cooling / Dry
Decision
Conditions
Heating
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Disconnection of fourway valve coil
Supposed
Defective fourway valve, coil, or harness
Causes
Defective outdoor unit PCB
Defective thermistor
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
119
(room thermistor temp. – indoor heat exchanger temp.) < –5°C (–9°F)
(indoor heat exchanger temp. – room thermistor temp.) < –5°C (–9°F)
SiUS091133
Service Diagnosis