Signal Transmission Error (Between Indoor Unit And Outdoor Unit) - Daikin FTXS30LVJU Service Manual

Inverter pair ftxs-l series fdxs-l series
Hide thumbs Also See for FTXS30LVJU:
Table of Contents

Advertisement

Troubleshooting
4.8
Signal Transmission Error (between Indoor Unit and
Outdoor Unit)
U4
Remote
Controller
Display
Method of
The data received from the outdoor unit in indoor unit-outdoor unit signal transmission is checked
whether it is normal.
Malfunction
Detection
Malfunction
The data sent from the outdoor unit cannot be received normally, or the content of the data is
Decision
abnormal.
Conditions
 Wiring error
Supposed
 Breaking of the connection wires between the indoor and outdoor units (wire No. 3)
Causes
 Defective outdoor unit PCB
 Defective indoor unit PCB
 Disturbed power supply waveform
109
SiUS091133
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents