Ol Activation (Compressor Overload) - Daikin FTXS30LVJU Service Manual

Inverter pair ftxs-l series fdxs-l series
Hide thumbs Also See for FTXS30LVJU:
Table of Contents

Advertisement

Troubleshooting

4.12 OL Activation (Compressor Overload)

E5
Remote
Controller
Display
Method of
A compressor overload is detected through compressor OL.
Malfunction
Detection
 If the error repeats, the system is shut down.
Malfunction
 Reset condition: Continuous run for about 60 minutes without any other error
Decision
 The operating temperature condition is not specified.
Conditions
 Defective discharge pipe thermistor
Supposed
 Defective electronic expansion valve or coil
Causes
 Defective FourWay valve or coil
 Defective outdoor unit PCB
 Refrigerant shortage
 Water mixed in refrigerant
 Defective stop valve
Troubleshooting
Check No.01
Refer to P.142
Check No.12
Refer to P.144
Check No.13
Refer to P.145
Check No.14
Refer to P.145
115
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Discharge pipe
thermistor disconnected?
NO
Check No. 01
Check the thermistors.
OK
Check No. 12
Check the electronic
expansion valve.
OK
Check No. 13
Check the four-way valve.
OK
Check No. 14
Check the refrigerant line.
OK
YES
NG
* Discharge pipe thermistor
NG
NG
NG
* Refrigerant shortage
* Water mixed
* Stop valve
SiUS091133
Insert the thermistor in
position.
Replace the discharge pipe
thermistor.
Replace the electronic
expansion valve or the coil.
Replace the four-way valve
or the coil.
Replace the outdoor unit
PCB.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
(R14438)