Troubleshooting
4.12 OL Activation (Compressor Overload)
E5
Remote
Controller
Display
Method of
A compressor overload is detected through compressor OL.
Malfunction
Detection
If the error repeats, the system is shut down.
Malfunction
Reset condition: Continuous run for about 60 minutes without any other error
Decision
The operating temperature condition is not specified.
Conditions
Defective discharge pipe thermistor
Supposed
Defective electronic expansion valve or coil
Causes
Defective FourWay valve or coil
Defective outdoor unit PCB
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
Troubleshooting
Check No.01
Refer to P.142
Check No.12
Refer to P.144
Check No.13
Refer to P.145
Check No.14
Refer to P.145
115
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Discharge pipe
thermistor disconnected?
NO
Check No. 01
Check the thermistors.
OK
Check No. 12
Check the electronic
expansion valve.
OK
Check No. 13
Check the four-way valve.
OK
Check No. 14
Check the refrigerant line.
OK
YES
NG
* Discharge pipe thermistor
NG
NG
NG
* Refrigerant shortage
* Water mixed
* Stop valve
SiUS091133
Insert the thermistor in
position.
Replace the discharge pipe
thermistor.
Replace the electronic
expansion valve or the coil.
Replace the four-way valve
or the coil.
Replace the outdoor unit
PCB.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
(R14438)
Service Diagnosis