Daikin FTXS30LVJU Service Manual page 115

Inverter pair ftxs-l series fdxs-l series
Hide thumbs Also See for FTXS30LVJU:
Table of Contents

Advertisement

Troubleshooting
Refrigerant shortage detection III: (09/12 class only)
When the difference of the temperature is smaller than L, it is regarded as refrigerant shortage.
Cooling
Heating
 If the error repeats, the system is shut down.
 Reset condition: Continuous run for about 60 minutes without any other error
 Disconnection of the discharge pipe thermistor, indoor or outdoor heat exchanger thermistor,
Supposed
Causes
 Closed stop valve
 Refrigerant shortage (refrigerant leakage)
 Poor compression performance of compressor
 Defective electronic expansion valve
105
room thermistor temperature – indoor heat exchanger temperature
outdoor heat exchanger temperature – outdoor temperature
indoor heat exchanger temperature – room thermistor temperature
outdoor temperature – outdoor heat exchanger temperature
room or outdoor temperature thermistor
SiUS091133
L
4.0°C (7.2°F)
4.0°C (7.2°F)
3.0°C (5.4°F)
3.0°C (5.4°F)
Service Diagnosis