Forced Cooling Operation - Daikin FTXS30LVJU Service Manual

Inverter pair ftxs-l series fdxs-l series
Hide thumbs Also See for FTXS30LVJU:
Table of Contents

Advertisement

SiUS091133

2. Forced Cooling Operation

Conditions
Start
Command
frequency
End
Others
 Indoor Unit
FTXS series
 Outdoor Unit
09/12 class
Trial Operation and Field Settings
Item
The forced cooling operation is allowed when both of the following conditions are
met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
The forced cooling operation starts when any of the following conditions is fulfilled.
1) Press the forced cooling operation [ON/OFF] button (SW1) on the indoor unit
for 5 seconds.
2) Press the forced cooling operation [ON/OFF] button (SW1) on the outdoor unit.
09/12 class: 58 Hz
15/18 class: 66 Hz
24 class: 31 Hz
30/36 class: 55 Hz
The forced cooling operation ends when any of the following conditions is fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation [ON/OFF] button (SW1) on the indoor unit
again.
3) Press the [ON/OFF] button on the remote controller.
4) Press the forced cooling operation [ON/OFF] button (SW1) on the outdoor unit.
Protection functions have priority over all other functions during forced cooling
operation.
ON/OFF button (SW1)
Forced cooling
operation
[ON/OFF] button
(SW1)
Forced Cooling
FDXS series
(R14145)
2
1
Push

Forced Cooling Operation

[ON/OFF] button (SW1)
3
Screwdriver
(R16614)
(R16615)