SiAF332111E

5.35 OL Activation (Compressor Overload)

Applicable
RXMQ6/8AR
Models
H5
Error Code
Method of Error
A compressor overload is detected through compressor OL.
Detection
Error Decision
 If the error occurs, the system is shut down.
Conditions
 Reset condition: Continuous run for about 60 minutes without any other error
Supposed
 Disconnection of discharge pipe thermistor
Causes
 Defective discharge pipe thermistor
 Disconnection of connector X3A (RXMQ6AR)
 Disconnection of connector X5A (RXMQ8AR)
 Disconnection of 2 terminals of OL (Q1M)
 Defective OL (Q1M)
 Broken OL harness
 Defective outdoor unit PCB
Part 6 Service Diagnosis