Error Messages and Alarm Outputs
Fatal Errors
Item
Cause
Power interrup-
Power interruption
tion
occurred and
lasted longer than
the specified limit.
Expansion CPU
Expansion CPU
Rack power
Rack
OFF
Power Supply Unit
is OFF.
CPU error
Watchdog timer
Memory error
Error occurred dur-
ing internal
memory and Ex-
pansion DM verifi-
cation.
I/O bus error
Erroneous data
transferred be-
tween CPU and I/O
Units
Duplicated
Rack numbers and
number
CPU Bus Unit unit
numbers or I/O
words are assigned
in duplicate.
CPU bus error
Error in data trans-
fer between CPU
and CPU Bus Unit
or watchdog timer
error in CPU Bus
Unit.
I/O points over
Too many I/O
points or too many
Units are registered
in the I/O table.
I/O setting error
Input/Output desig-
nation is wrong for
I/O Unit.
Program error
END(001) is miss-
ing, or the capacity
of the user memory
is exceeded.
Cycle time over
Cycle time monitor
time is exceeded.
Fatal SFC error
SFC syntax error.
System failure
FALS was ex-
(FALS)
ecuted in program.
CPU indicators
Power RUN ERROR WDT ALARM OUT INT COMM
Unlit
Unlit
Unlit
Unlit
Lit
Unlit
Unlit
Unlit
Lit
Unlit
---
Lit
Lit
Unlit
Lit
---
Lit
Unlit
Lit
---
Lit
Unlit
Lit
---
Lit
Unlit
Lit
---
Lit
Unlit
Lit
---
Lit
Unlit
Lit
---
Lit
Unlit
Lit
---
Lit
Unlit
Lit
---
Lit
Unlit
Lit
---
Lit
Unlit
Lit
---
Unlit
Unlit
Unlit
Unlit
Unlit
Unlit
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Section 5-1
Peripheral
Device error
message
POWER FAIL
POWER FAIL
WDT ERR
MEMORY ERR
I/O BUS ERR
NO DUPL ERR
CPU BUS ERR
I/O OVER
I/O SET ERR
NO END
INSTR
PROGRAM
OVER
SCAN TIME
OVER
SFC ERR
SYSTEM FAL
77