Omron CV500 Installation Manual page 120

Sysmac cv-series
Hide thumbs Also See for CV500:
Table of Contents

Advertisement

Power Supply Units
Item
Supply voltage
100 to 120 or 200 to 240 VAC, 50/60 Hz
Operating voltage
85 to 132 or 170 to 264 VAC
range
Power
150 VA max.
consumption
Inrush current
30 A max.
Output capacity
8 A, 5 VDC
Insulation
20 M
resistance
Dielectric
2,300 VAC 50/60 Hz for 1 min between AC external and
strength
leakage current: 10 mA max.
1,000 VAC 50/60 Hz for 1 min between DC external and
leakage current: 20 mA max. (See note 1.)
Noise immunity
1,000 Vp-p, pulse width: 100 ns to 1 s, rise time: 1 ns (via noise simulation)
Vibration
10 to 58 Hz, 0.075-mm amplitude, 58 to 150 Hz, acceleration: 9.8 m/s
resistance
directions for 80 minutes (Time coefficient; 8 minutes x coefficient factor 10 = total time 80 minutes)
(according to JIS C0040)
Shock resistance
147 m/s
Ambient
Operating: 0 to 55 C
temperature
Storage: –20 to 75 C (except Memory Card and battery)
Humidity
10% to 90% (with no condensation)
Atmosphere
Must be free from corrosive gasses
Grounding
Less than 100
Enclosure
Mounted in a panel
Weight
All models are each 9 kilograms max.
Dimensions
CPU (10 slots)/Expansion CPU/Expansion I/O (11 slots): 480 x 250 x 123 mm (WxHxD)
(without cables,
CPU (5 slots)/Expansion I/O (6 slots): 306 x 250 x 123 mm (WxHxD)
see note 3)
CPU (3 slots)/Expansion I/O (4 slots): 236 x 250 x 123 mm (WxHxD)
Note 1. Disconnect the
insulation and dielectric strength tests. If the tests are repeatedly performed with the
terminals short-circuited, the internal components may be damaged.
2.
Acceleration (G)
3.
H
Appendix B
Specifications
CVM1-PA208
min. (at 500 VDC) between AC external terminals and
2
3 times each in X, Y, and Z directions (according to JIS C0041)
(LG) terminal of the Power Supply Unit from the
Amplitude:
0.075 mm
Frequency (Hz)
W
CV500-PS221
200 VA max.
12 A, 5 VDC
(GR) terminals,
(GR) terminals,
CV500-PS211
24 VDC
20.4 to 28.8 VDC
100 W max.
30 A max.
12 A, 5 VDC
(GR) terminals. (See note 1.)
2
(see note 2) in X, Y, and Z
(GR) terminal when performing
(LG) and
D
(GR)
107

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cv2000Cv1000Cvm1Sysmac cv seriesSysmac cv500Sysmac cv1000 ... Show all

Table of Contents