Omron CV500 Installation Manual page 128

Sysmac cv-series
Hide thumbs Also See for CV500:
Table of Contents

Advertisement

Specifications
Dynamic DC Input Unit
Input Voltage
24 VDC
Input Impedance
2.2 k
Input Current
10 mA typical (at 24 VDC)
ON Voltage
10.2 VDC min.
OFF Voltage
3.0 VDC max.
ON Delay
1.5 ms max.
OFF Delay
1.5 ms max.
Circuit Configuration
COM
(24 V)
DATA 0
2.2 k
to
DATA 7
2.2 k
24 V
STB 0
Inter-
to
nal
STB 7
Circuit
COM
(0 V)
No. of Inputs
64, dynamic
Internal Current
300 mA, 5 VDC max.
Consumption
Weight
450 grams max.
Dimensions
A-shape
Wiring Dynamic Inputs
When a large number of bits must be controlled, an ID212 DC Input Unit can simplify wiring by inputting status to up
to 64 bits through only 16 points. Using digital switches or a specially wired keyboard, the different combinations of
input points will determine which bits are ON. Two examples of connections using digital switches or a keyboard
are given.
Inputs
+10%
/
–15%
General Specifications
560
560
Inter-
nal
Circuit
3G2A5-ID212
Max. Switching
Capacity
Leakage Current
Residual Voltage
ON Delay
OFF Delay
Power for
External Supply
Terminal Connections
24 VDC
Refer to p 116 for connections.
Appendix B
Outputs
+10%
0.1A, 24 VDC
/
–15%
0.1 mA max.
1.5 V max.
0.2 ms max.
0.3 ms max.
24 VDC
10%
0
DATA 0
1
DATA 1
2
DATA 2
3
A
DATA 3
4
DATA 4
5
DATA 5
6
DATA 6
7
DATA 7
8
COM (24 V)
9
STB 0
10
STB 1
11
STB 2
12
STB 3
13
STB 4
14
STB 5
15
STB 6
16
STB 7
+
17
COM (0 V)
18
24 V
19
NC
115