Power Supply Units
!
Caution
WARNING
!
Caution
!
56
Use round crimp terminals for wiring. Do not connect bare stranded wires direct-
ly to terminal blocks. Use M3.5 screws for tightening crimp terminals.
7 mm max.
Tighten the screws on the terminal block of the AC Power Supply Unit to a torque
of 0.8 N m. The loose screws may result in short-circuit, burning, or malfunc-
tion.
20 mm max.
Tightening torque: 0.8 N m
Always attach crimp terminals to the wires to ensure proper connection.
Connecting loose wires can cause fires.
Abide by the following precautions when wiring the Power Supply Units. Failure
to abide by these precautions my cause faulty operation or damage to the Unit.
Be sure that no wire clippings or other foreign materials enter the Units when
wiring.
Check and recheck all wiring before supplying power to the system.
Note The RUN output on Slave Racks will go OFF when a remote I/O error occurs.