Specifications
Triac Output Units Continued
Item
Max. Switching Capacity
Max. Inrush Current
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Delay
OFF Delay
No. of Outputs
Internal Current Consumption
Fuse Capacity
Weight
Circuit Configuration
Terminal Connections
Dimensions
1.2 A, 250 VAC, 50/60 Hz (4 A/common, 5 A/Unit)
15 A (pulse width: 100 ms)
30 A (pulse width: 10 ms)
100 mA, 10 VAC
50 mA, 24 VAC
10 mA, 100 VAC
10 mA, 240 VAC
1.5 mA (120 VAC, 60 Hz) max.
3.0 mA (240 VAC, 60 Hz) max.
1.5 VAC (100 to 600 mA) max.
1.5 VAC (50 to 100 mA) max.
5.0 VAC (10 to 50 mA) max.
1 ms max.
1/2 of load frequency + 1 ms max.
16 (8 outputs/common, 2 circuits)
450 mA, 5 VDC max.
5 A, 250 V, 6.35 dia. x 32 (2 fuses)
600 grams max.
The fuse is 5 A, 250 V and 6.35 mm dia. x 32 mm.
250 VAC max.
250 VAC max.
C-shape
C500-OA226
f Ω
f Ω
0.022 F
Fuse/
fuse blowout
detection circuit
f Ω
f Ω
0.022 F
Fuse/
fuse blowout
detection circuit
0
0
L
1
1
L
2
2
L
3
3
L
4
4
L
~
5
5
L
6
6
L
7
7
L
COM
8
8
9
L
9
10
L
10
11
L
11
12
L
12
13
L
~
13
14
L
14
15
L
15
16
L
COM
17
18
NC
19
NC
Appendix B
OUT 00
to
OUT 06
OUT 07
COM
OUT 08
to
OUT 14
OUT 15
COM