Specifications
Special Considerations for C500-OA225
The maximum current value allowed per output point depends on the ambient temperature and the number of
points per common that are ON simultaneously. The graph below shows the relationship between the allowable
current per point and the number of points ON per common. Be sure not to exceed the values shown in the graph.
Current
value per
point (A)
Number of Points per Common Turned ON Simultaneously
The graph below shows the value of the surge current and the time it takes the current to reach a steady state
(current-carrying time). The curved line in the graph represents the maximum value of surge current at which the
Unit can operate properly. It is suggested that when opening and closing a load with a large surge current, to keep
the value of the surge current to half the value shown the graph (within the shaded area).
124
1.0
0.8
0.6
0.4
0.2
0
1
2
3
4
5
Number of points per common that
can be turned ON simultaneously.
Surge
15
Current
(A. Peak)
10
5
0
10
30
50
Current-carrying time (ms)
Environment temperature
25 C
40 C
55 C
6
7
8
100 200
500
1,000
5.000
Appendix B