Specifications
Triac Output Units
Item
Max. Switching
1 A, 132 VAC, 50/60 Hz (4 A/common, 5 A/Unit) 1 A, 250 VAC, 50/60 Hz (4 A/common, 5 A/Unit)
Capacity
Min. Switching
10 mA (resistive load) , 10 VAC
Capacity
40 mA (inductive load), 10 VAC
Leakage Current
3 mA (100 VAC) max.
Residual Voltage
1.2 V max.
ON Delay
1 ms max.
OFF Delay
1/2 of load frequency max.
No. of Outputs
16 (8 outputs/common, 2 circuits)
Internal Current
300 mA, 5 VDC max.
Consumption
Fuse Capacity
5 A, 250 V (two fuses)
Weight
500 grams max.
Circuit
Configuration
Inter-
nal
Circuit
The fuse is 5 A, 250 V and 6.35 mm dia. x 32 mm.
Terminal
Connections
Dimensions
A-shape
122
3G2A5-OA121
22
0.022 F
Fuse/fuse blowout
detection circuit
22
0.022 F
Fuse/fuse blowout
detection circuit
0
L
1
L
2
L
3
L
4
L
132 VAC max.
~
5
L
6
L
7
L
COM
8
L
9
10
L
10
11
L
11
12
L
12
13
L
132 VAC max.
~
13
14
L
14
15
L
15
16
L
COM
17
18
NC
19
NC
10 mA (resistive load), 10 VAC
40 mA (inductive load), 10 VAC
3 mA max. at 100 VAC
6 mA max. at 200 VAC
1.2 V max.
1 ms max.
1/2 of load frequency max.
16 (8 outputs/common, 2 circuits)
300 mA, 5 VDC max.
5 A, 250 V (two fuses)
500 grams max.
OUT 00
to
Inter-
OUT 06
OUT 07
nal
COM
Circuit
OUT 08
to
OUT 14
OUT 15
COM
The fuse is 5 A, 250 V; 6.35 mm dia. x 32 mm.
0
1
2
3
4
250 VAC max.
5
6
7
8
9
250 VAC max.
A-shape
Appendix B
3G2A5-OA222
OUT 00
22
0.022 F
OUT 06
Fuse/fuse blowout
OUT 07
detection circuit
COM
OUT 08
22
0.022 F
OUT 14
Fuse/fuse blowout
OUT 15
detection circuit
COM
0
0
L
1
1
L
2
2
L
3
3
L
4
4
L
~
5
5
L
6
6
L
7
7
L
COM
8
8
9
L
9
10
L
10
11
L
11
12
L
12
13
L
~
13
14
L
14
15
L
15
16
L
COM
17
18
NC
19
NC
to
to

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cv2000Cv1000Cvm1Sysmac cv seriesSysmac cv500Sysmac cv1000 ... Show all

Table of Contents