3.3.14 setuP | Load shed WindoW (raychem nGC-20 onLy)

This window enables or disables the various load shed zones. The actual configuration and
implementation of these zones are done in Raychem Supervisor.
Fig. 3.20 SETUP|LOAD SHED window
Each independent Raychem NGC-20 controller can be assigned to none, some or all of the 16
independent zones. Those zones that have been assigned to the Raychem NGC-20 controller
requires the Enable box to be checked for the Load Shedding process to activate.
If the Failsafe box is checked, the Raychem NGC-20 controller will revert to the failsafe mode
configured in the Setup|Circuit window if the Raychem NGC-20 controller loses communication
with Raychem Supervisor.

3.3.15 status | CirCuit WindoW

The status Circuit window displays the status information for individual Circuits. Data in the status
menus cannot be changed; it is informational only.
industrial heat tracing solutions
EN-RaychemNGC30UIT2Programming-AR-H58186      02/16
44 / 84