Siemens SINUMERIK 805 Operating Instructions Manual page 231

Table of Contents

Advertisement

06.90
6 Monitoring
8.3.3 List of alarms
6159
Runtime exceeded
step 5
program
The max. runtime
in
PLC-MD
1
has been exceeded
PLC-STOP, dependent
on PLC-MD 2003 bit
1
Evaluate DB diagnostics!
Increase MD
1
Set MD 2003 bit 6
Time optimization
of
PLC
program
Cause:
Effect:
Explanation:
Remedy:
CPU load increases
Cycle time increases
6160
Runtime exceeded 0B 2
The max. runtime
in
PLC-MD has been exceeded
PLC-STOP, dependent on PLC-MD 2003 bit 0
Evaluate DB
diagnostics!
Increase MD
3
Time
optimization of
OB
2
Cause:
Effect:
Explanation:
Remedy:
6161
Cycle time exceeded
The
max. runtime in PLC-MD 5 has been exceeded
PLC-STOP
Note: bit commands only
have a processing time of
approx.
1
ps!
Increase MD 5
Time optimization of PLC program
Cause:
Effect:
Explanation:
Remedy:
6162
Processing
delay OB 2
The
alarm program (OB
2)
has interrupted itself
PLC-STOP, dependent
on PLC-MD 2003 bit 0
Evaluate DB
diagnostics
Time
optimization of OB
2,
i.e.
reduce the processing time of the
alarm program!
Cause:
Effect:
Explanation:
Remedy:
6164
DHP protec. function output (short-circuit)
Short-circuit
at
a DMP submodule
output
Evaluate DB
1
diagnostics
Cause:
Remedy:
®
Siemens AG
1990 All Rights
Reserved
6ZB5 410-0EE02