Appendix A: Reporting Formats - Fire-Lite UDACT-F Instruction Manual

Universal digital alarm communicator / transmitter
Table of Contents

Advertisement

Appendix A
Table A-1 shows the data reporting structure for each of the pulsed formats as well as the Ademco Express formats.
Ademco Express formats allow a typical data message to be transmitted to the Central Station in under five seconds.
Pulsed formats typically require 15 to 20 seconds in comparison. Table A-2 on page 48, defines each letter code used
in Table A-1 . Table A-3 on page 49, describes the data reporting structure used for Ademco Contact ID format.
Data Reporting Structure
TABLE A-1:
Report
Alarm
Alarm Restore
Zone Trouble
(Zone Open)
Zone Trouble Restore
System Trouble
System Trouble Restore
Low Battery
Low Battery Restore
AC Loss
AC Loss Restore
Supervisory Condition
Supervisory Condition Restore
Test Report
Abnormal Test Report
Notes:
Refer to Table A-2 on page 48, for an explanation of each letter code in Table A-1 .
Refer to Table B-1 on page 51, for a list of compatible receivers.
Reporting Formats
Format #
0, 2, 4, 6, 8
3+1/4+1/Standard
4+1 Express
SSS(S) A
SSS(S) RA
SSS(S) RTZ
SSS(S) RTZ
SSS(S) TS
SSS(S) RTS
SSS(S) L
SSS(S) RL
SSS(S) P
SSS(S) RP
SSS(S) V
SSS(S) RV
SSS(S) X
SSS(S) XA
Document #50049
Format #
4+2/Standard
4+2 Express
SSSS AA2
SSSS RARA2
SSSS TZTZ2
SSSS RTZRTZ2
SSSS TSTS2
SSSS RTSRTS2
SSSS LL2
SSSS RLRL2
SSSS PP2
SSSS RPRP2
SSSS VV2
SSSS RVRV2
SSSS XX2
SSSS XAXA2
Rev. E0
01/22/01
P/N 50049:E0
Reporting Formats
1, A, C
47