Cisco Nexus 2000 Series Installation Manual page 92

Hide thumbs Also See for Nexus 2000 Series:
Table of Contents

Advertisement

Cisco Nexus 2248TP-E FEX
Table 3-1
Dimensions
Width
Depth
Height
Weight
1. Measured with two power supplies and one fan module installed.
You can order the Cisco Nexus 2248TP-E FEX with port-side exhaust or port-side intake airflow and
with AC or DC power supplies. If you are going to install the port side in a hot aisle, then order
port-side-exhaust airflow for all of the fan trays and power supplies. If you are going to install the port
side in the cold aisle, order port-side-intake airflow for all of the fan trays and power supplies.
For visual identification, port-side-intake airflow power supplies and fan trays have a black stripe across
Note
their front, and port-side-exhaust airflow modules do not have a black stripe across their front. All of the
power supplies and fan trays must have the same direction of airflow for the components to properly
function (all of these components must either have a black stripe or all of the components must not have
a black stripe).
The front of the Cisco Nexus 2248TP-E FEX chassis has one or two power supplies, a fan tray, and two
chassis LEDs as shown in
redundancy, you must install a second power supply.
Figure 3-1
1
1
Power supply
2
Fan tray
Cisco Nexus 2000 Series Hardware Installation Guide
3-2
Physical Characteristics for the Cisco Nexus 2248TP-E FEX
1
Figure
3-1. This FEX model requires one power supply, but if you want power
Front View of the Cisco Nexus 2248TP-E Chassis
2
Chapter 3
Using a Fabric Extender with a Cisco Nexus 9000 Series Switch
17.3 inches (43.9 cm)
20.0 inches (50.8 cm)
1.72 inches (4.4 cm)
17.7 lb (8.0 kg)
3
4
3
Power supply (blank shown)
4
Status (top) and ID (bottom) LEDs

Advertisement