The number of attributes available for each trap is shown below:
Specific Number
1
2
3
4
The information of the attributes present is shown in the following:
Specific Trap #1:
Attribute #1 – MIB value upsBatteryStatus. Integer value 1 to 4 that indicates battery health.
Attribute #2 – MIB value upsSecondsOnBattery. Integer value that represents the amount of time, in
consecutive seconds, that the UPS has been in battery backup operation mode.
Attribute #3 – MIB value upsEstimatedMinutesRemaining that represents the amount of time, in minutes,
that the UPS can currently provide battery backup, should backup operation be necessary.
Specific Trap #2:
Attribute #1 – MIB value upsTestID. Integer value that represents the test. This number resets to value 0
each time RemotEye II is reset.
Attribute #2 – MIB value upsTestSpinLock. Integer value that acts as a key granting or refusing
permission to initiate a test.
Attribute #3 – MIB value upsTestResultsSummary. Integer value that represents the results of a test.
Specific Trap #3:
Attribute #1 – MIB value upsAlarmID. This is an integer representing the sequence in which the trap was
added to the alarms browser. This sequence will repeat when the agent is reset.
Attribute #2 – MIB value upsAlarmDesc. This is a MIB Description (whether numerical or textual) of the
fault that has added.
Specific Trap #4:
Attribute #1 – MIB value upsAlarmID. This is an integer representing the sequence in which the trap was
cleared from the alarms browser. This sequence will repeat when the agent is reset.
Attribute #2 – MIB value upsAlarmDesc. This is a MIB Description (whether numerical or textual) of the
fault that has cleared.
RemotEye II User Manual – 50024-014
Description
UPS On Battery
UPS Test Completed
UPS Alarm Added
UPS Alarm Removed
Number of Available
Attributes
3
3
2
2
77