03-13

Analog Input Noise Filter

Settings
0.00~2.00 Sec
Interferences commonly exist with analog signals, such as those entering AVI, ACI and AUI.
These interferences constantly affect the stability of analog control and using the Input
Noise Filter will create a more stable system.
If Pr. 03-13 is large, the control will be stable, yet the response to the input will be slow. If
Pr. 03-13 is small, the control may be unstable, yet the response to the input will fast.
03-14

Loss of the ACI signal

Settings
This parameter determines the operation of the drive when the 4~20mA (ACI) signal is lost.
03-15

Analog Output Selection

Settings
0-24
Full List of the Functions
Settings
Functions
Output frequency
0
1
Command frequency
2
Speed
3
Current
4
Output voltage
5
DC BUS voltage
6
Power factor
7
Power
8
Torque
9
AVI
10
ACI
11
AUI
12
Torque current command
13
Torque current estimation
14
Exciting magnet current
command
15
Magnetic flux current
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
0
disabled
1
continue operation at last known frequency
2
decelerate to a stop
3
stop immediately and display E.F.
01-00=100%
01-00=100%
01-00=100%
rated current of the inverter =100%
200V (400V) =100%
400V (800V) =100%
-1.000~1.000=100%
rated power of the inverter =100%
full-load torque =100%
(0~10V=0~100%)
(0~20mA=0~100%)
(-10~10V=0~100%)
rated current of the inverter =100%
rated current of the inverter =100%
rated current of the inverter =100%
rated current of the inverter =100%
Explanations
5-33
VFD-V Series
Factory setting 0.10
Factory setting 0
Factory setting 0
5