Source Of The Frequency Command; Source Of The Operation Command; Stop Methods - Delta VFD-V Series User Manual

Flux vector control ac motor drivers
Table of Contents

Advertisement

00-20

Source of the Frequency Command

Settings
This parameter determines the drive's master frequency source and Master torque
source.
00-21

Source of the Operation Command

Settings
This parameter sets the drive's operation command source, which may also be switched
via the PU key on the digital keypad. When the PU led on the keypad is illuminated the
Keypad has control over the drives operation.
00-22

Stop Methods

Settings
When a "STOP" command is received, the drive will follow the stop method programmed
this parameter.
Frequency
Output
Frequency
Operation
Command
RUN
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
0 The digital keypad
1 The RS485 communication input
2 The external analog input
3 The external up/down pins (multi-function input terminals)
4 The pg (encoder) input or clock
5 The RS485 and PU05 at the same time (dual source)
6 The clock and direction (set by 10-12)
0 The RS485 communication
1 The external terminal operation (2 wire or three wire)
2 The digital keypad operation
0 Ramp to stop
1 Coast to stop
Time
STOP
Output
Frequency
Operation
Command
RUN
5-11
VFD-V Series
Factory setting 0
Factory setting 0
Factory setting 0
Time
Free running
to stop
STOP
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents