Maximum Output Frequency; Maximum Output Voltage; Upper Midpoint Output Voltage; Group 1: Basic Parameter - Delta VFD-V Series User Manual

Flux vector control ac motor drivers
Table of Contents

Advertisement

5.2 Group 1: Basic Parameter

01-00

Maximum Output Frequency

Settings
50.0~400.00Hz
This parameter determines the drive's maximum output frequency.
01-01
Maximum Voltage Frequency (Base Frequency)
Settings
0.00~400.00 Hz
This parameter must be set to the motor's nameplate frequency rating.
01-02

Maximum Output Voltage

Settings
230V: 0.0~255.0V
460V: 0.0~510.0V
This parameter must be set to the motor's nameplate voltage rating.
01-03
Upper Midpoint Output Frequency
Settings
0.00~400.00Hz
01-04

Upper Midpoint Output Voltage

Settings
230V: 0.0~255.0V
460V: 0.0~510.0V
01-05
Lower Midpoint Output Frequency
Settings
0.00~400.00Hz
01-06
Lower Midpoint Output Voltage
Settings
230V: 0.0~255.0V
460V: 0.0~510.0V
01-07
Minimum Output Frequency
Settings
0.00~400.00Hz
01-08
Minimum Output Voltage
Settings
230V: 0.0~255.0V
460V: 0.0~510.0V
Setting of the V/F curve figure is usually based upon the motor's allowable loading
characteristics. Pay special attention to the motor's heat dissipation, dynamic balance,
and bearing lubricity, if the loading characteristics exceed the loading limit of the motor.
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Factory setting 60.00/50.00
Factory setting 60.00/50.00
Factory setting 220.0
Factory setting 440.0
Factory setting 0.50
Factory setting 5.0
Factory setting 10.0
Factory setting 0.50
Factory setting 5.0
Factory setting 10.0
Factory setting 0.00
Factory setting 0.0
Factory setting 0.0
5-13
VFD-V Series
5