2-Wire/3-Wire Operation Control; Group 2: Digital Output/Input Parameter - Delta VFD-V Series User Manual

Flux vector control ac motor drivers
Table of Contents

Advertisement

5.3 Group 2: Digital Output/Input Parameter

02-00

2-Wire/3-Wire Operation Control

Settings
The VFD-V drive offers six types of external operation control.
Three of
six methods include a "Line Start Lockout" feature. When Line
the
start lock out is enabled, the drive will not recognize a RUN command upon
power up. The VFD-V must see the terminal state change from low to high.
This is a safety feature for applications where applying power does not
determine a RUN command.
The Line Start Lockout feature does not guarantee the motor will never start under this
condition. It is possible the motor may be set in motion by a malfunctioning switch.
02-00
0, 1
2-wire operation control (1)
FWD/STOP
REV/STOP
2, 3
2-wire operation control (2)
RUN/STOP
REV/FWD
4, 5
3-wire operation control
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
0
FWD/STOP, REV/STOP
1
FWD/STOP, REV/STOP (Line Start Lockout)
2
RUN/STOP, REV/FWD
3
RUN/STOP, REV/FWD (Line Start Lockout)
4
3-wire (momentary push button)
5
3-wire (momentary push button and Line Start Lockout)
Control Circuits of the External Terminal
FWD/STOP
REV/STOP
RUN/STOP
FWD/REV
STOP
RUN/FWD
5-19
FWD:("OPEN":STOP)
REV:("OPEN": STOP)
DCM
FWD:("OPEN":STOP)
REV:("OPEN": FWD)
DCM
RUN
FWD "CLOSE":RUN
EF/MI1 "OPEN":STOP
REV/FWD "OPEN": FWD
DCM
VFD-V Series
Factory setting 0
("CLOSE":FWD)
("CLOSE": REV)
VFD-V
("CLOSE":RUN)
("CLOSE": REV)
VFD-V
"CLOSE": REV
VFD-V
5