Analog Input/Output Parameters For Extension Card - Delta VFD-E User Manual

High performance/flexible options/ micro type ac motor drives
Hide thumbs Also See for VFD-E:
Table of Contents

Advertisement

Parameter
Explanation
Group 12: Analog Input/Output Parameters for Extension Card
Parameter
Explanation
AI1 Function
12.00
Selection
AI1 Analog Signal
12.01
Mode
Min. AVI3 Input
12.02
Voltage
Min. AVI3 Scale
12.03
Percentage
Max. AVI3 Input
12.04
Voltage
Max. AVI3 Scale
12.05
Percentage
Min. ACI2 Input
12.06
Current
Min. ACI2 Scale
12.07
Percentage
Max. ACI2 Input
12.08
Current
Max. ACI2 Scale
12.09
Percentage
Revision November 2007, 03EE, SW--PW V1.10/CTL V2.10
Settings
22: Source of second frequency command
23: Run/Stop PLC Program (PLC1)
(NOT for VFD*E*C models)
23: Quick Stop (Only for VFD*E*C models)
24: Download/execute/monitor PLC Program
(PLC2) (NOT for VFD*E*C models)
Settings
0: Disabled
1: Source of the 1st frequency
2: Source of the 2nd frequency
3: PID Set Point (PID enable)
4: Positive PID feedback
5: Negative PID feedback
0: ACI2 analog current (0.0 ~ 20.0mA)
1: AVI3 analog voltage (0.0 ~ 10.0V)
0.0 to 10.0V
0.0 to 100.0%
0.0 to 10.0V
0.0 to 100.0%
0.0 to 20.0mA
0.0 to 100.0%
0.0 to 20.0mA
0.0 to 100.0%
Chapter 4 Parameters|
Factory
Setting
Factory
Setting
0
1
0.0
0.0
10.0
100.0
4.0
0.0
20.0
100.0
Customer
Customer
4-25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents