02-18

Digital Output Gain

Settings
1~40
This parameter determines the signals of the drive's digital output terminal (DFM-DCM)
and of the digital frequency output (pulse, work period = 50%). Output pulse per
second = output frequency × (Pr. 02-17)。
Setting of the multiple has a lot to do with the carrier frequency; the carrier frequency has
to be greater than "2 x maximum operation frequency x multiplying rate".
02-19

Pre-set Arrival Frequency 1

Settings
0.00~400.00Hz
02-20
Pre-set Arrival Frequency 1 Width
Settings
0.00~400.00Hz
02-21
Pre-set Arrival Frequency 2
Settings
0.00~400.00Hz
02-22
Pre-set Arrival Frequency 2 Width
Settings
0.00~400.00Hz
Once the drive's output speed (frequency) achieves the arbitrary designated (speed)
frequency, and that if the corresponding multi-function output terminal is set as 2~7 or
24~27 (Pr. 02-10~02-14), then the multi-function output terminal contact will be "closed".
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
02-16=3
02-12=22
02-13=21
5-27
Trigger signal width
02-15=5
Factory setting
Factory setting 60.00/50.00
Factory setting 2.00
Factory setting 60.00/50.00
Factory setting 2.00
VFD-V Series
0.5ms
0.5ms
1
5