Pid Frequency Output Command Limit; Pid Deviation Range; One-Time Delay - Delta VFD-V Series User Manual

Flux vector control ac motor drivers
Table of Contents

Advertisement

VFD-V Series
08-05

PID Frequency Output Command limit

Settings
0.0~100.0%
This parameter determines the limit of the PID Command frequency. If this parameter
is set to 120%, then the maximum output frequency while in the PID operation will be
(120% x Pr.01-00) 72%.
08-06

PID Deviation Range

Settings
-100.0~+100.0%
08-07

One-Time Delay

Settings
0.000~0.005 Sec
Input Selection of the
PID Targeted Value
00-14=17:PID
command
00-14=18 display of the
PID feedback
Input Selection
of the PID Feedback
10-00:AVI/ACI
AUI/PG
PI Control: controlled by the P action only, and thus, the deviation cannot be eliminated
entirely. To eliminate residual deviations, the P + I control will generally be utilized.
And when the PI control is utilized, it could eliminate the deviation incurred by the
targeted value changes and the constant external interferences. However, if the I
action is excessively powerful, it will delay the responding toward the swift variation.
The P action could be used solely on the loading system that possesses the integral
components.
08-00=0
PID Cancelled
or 02-01~06=24(pid off)
1
2
Error Range Output
03-13=20
P
+
Proportion
Differential
gain
Time
-
08-01
I
08-02
One-Time Delay
PID Deviation Range
08-06
D
+
+
+
08-03
03-13=21
08-04
Integral's
Upper
Bound Freq.
5-60
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Factory setting
100.0
Factory setting
0.0
Factory setting
0.000
Output
One-Time
Delay
08-05
08-07
Treatment of the
Feedback Signal Fault
If Hz>08-05
time over08-08
=>08-09