Side Vent Configuration with Horizontal Termination (with vertical rise)

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and diffuser
positions.
Up to four elbows (45° or 90°) may be used.
Only one horizontal elbow may be used.
22' max (6.7m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
© Travis Industries
Installation
(for qualified installers only)
Exhaust Restrictor # 4
Intake Restrictor # 2
Diffuser Position # 2 (stock)
Exhaust Restrictor # 4
Intake Restrictor # 1
Diffuser Position # 1
H1
4090507
Exhaust Restrictor # 2 (stock)
Intake Restrictor # 1 (stock)
Diffuser Position # 1
H2
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
This is considered a
vertical elbow
22' max (6.7m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
100-01217_000