Top Vent Configuration With Vertical Termination - Travis Industries GREEN SMART 864 Installation Manual

See through fireplace
Table of Contents

Advertisement

Top Vent Configuration with Vertical Termination

The termination must
fall within the shaded
area shown in the chart.
Use the indicated
restrictor and diffuser
positions.
Up to four elbows (45°
or 90°) may be used.
Only one horizontal
elbow may be used.
May use 8" (203mm) or
6-5/8" (168mm)
diameter vent (see
page for 18 details).
© Travis Industries
Installation
(for qualified installers only)
40' max (12m)
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
4090507
Exhaust Restrictor # 4
Intake Restrictor # 2
Diffuser Position # 2 (stock)
Exhaust Restrictor # 3
Intake Restrictor # 2
Diffuser Position # 2 (stock)
H2
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
H1
This is considered a
vertical elbow
27
40' max (12m)
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
100-01217_000