Configuring the Thermostat Controller

The thermostat controller ships from the factory with
default settings for all configurable parameters. The
default settings are shown in Table 6. To reconfigure
the parameters, follow the steps in this section.
1. To access the Installer Configuration Menu, press
and hold the center key for approximately
8 seconds.
Note: If the Password parameter is configured,
Password 0 appears on the thermostat controller
display indicating that the configured password is
required to proceed.
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
St-By Heat
Occ Heat
= 69°F
= 72°F
Room Temperature
Figure 13: Increasing Room Temperature Setpoints
Stand-By
= 2 Hours
Unoccupied Time
= 6 Hours
Stand-By Time Elapsed
= Stand-By Mode
Unoccupied Time Elapsed
Stand-By
= 2 Hrs
Unoccupied Time
Stand-By Time Elapsed
= Stand-By Mode
Occ Cool
= 75°F
Time
First Movement
= Unoccupied Mode
by PIR Device
Last Movement Detected
= 0 Hours
Time
First Movement Detected
by PIR Device
Last Movement Detected
by PIR Device
Use the UP/DOWN arrow keys to indicate the
configured password, then press the MODE key to
proceed through the Installer Configuration Menu
parameters.
2. Once the Installer Configuration Menu begins,
press and release the center key to scroll through
the parameters listed in Table 6.
3. When the desired parameter is displayed, use the
UP/DOWN arrow keys to choose the desired
selection option.
4. Press and release the center key to continue
scrolling through the parameters.
Capability, Fan Control, and Occupancy Sensing Capability
St-By Cool
= 78°F
Stand-By
= 2 Hrs
Unoccupied Time
Stand-By Time Elapsed
= Stand-By Mode
Detected
by PIR Device
Stand-By
= 2 Hrs
Unoccupied Time
= 0 Hours
Stand-By Time Elapsed
= Stand-By Mode
= 6 Hours
Time
Time
11