Johnson Controls TEC2003-3 Installation Manual
Johnson Controls TEC2003-3 Installation Manual

Johnson Controls TEC2003-3 Installation Manual

Tec series multi-stage wireless thermostat controller

Advertisement

Quick Links

TEC2003-3 Multi-Stage Wireless Thermostat Controller

Installation Instructions

TEC2003-3
Applications
The TEC Series Wireless Thermostat Controller
System provides wireless networked control of
Heating, Ventilating, and Air Conditioning (HVAC)
equipment on a Building Automation System (BAS)
that enables remote monitoring and programming. This
TEC Series System integrates into a supervisory
controller using BACnet® Internet Protocol (IP) or
BACnet Master-Slave/Token-Passing (MS/TP)
communications.
TEC20 Coordinators allow the supervisory controller to
communicate with multiple TEC Wireless Thermostat
Controllers.TEC200x-3 Series Wireless Thermostat
Controllers provide networked control of a variety of
staged equipment. TEC2003-3 Multi-Stage Wireless
Thermostat Controllers control multi-stage packaged
heating/cooling equipment.
The wireless mesh network uses ZigBee™ technology
to enable remote monitoring and programming and to
enhance reliability by providing redundant transmission
paths through other TEC Wireless Thermostat
Controllers, creating a resilient, self-healing mesh
network.
IMPORTANT: The TEC2003-3 Wireless
Thermostat Controller is intended to provide an input
to equipment under normal operating conditions.
Where failure or malfunction of the thermostat
controller could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or
protect against failure or malfunction of the
thermostat controller.
TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions
Part No. 24-9890-730, Rev. B
North American Emissions Compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment is
operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area is
likely to cause harmful interference, in which case
the user will be required to correct the interference
at his/her own expense.
RF Transmitters: Compliance Statement
(Part 15.19)
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference,
and
2. This device must accept any interference
received, including interference that may cause
undesired operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by
the party responsible for compliance could void the
user's authority to operate the equipment.
Issued April 7, 2009
Supersedes June 20, 2008
1

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls TEC2003-3

  • Page 1: Installation Instructions

    TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions...
  • Page 2: Mounting The Thermostat Controller

    4. Pull approximately 152 mm (6 in.) of wire from the wall, and insert the wire through the hole in the Through Walls 10 m (30 ft) mounting base. Open Space 30 m (100 ft) TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions...
  • Page 3 5. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the cover. See Figure 5, Figure 6, and Table 2 for information on wiring the thermostat controllers. Figure 4: Removing the Screw Terminal Blocks TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions...
  • Page 4 If using the same power source Room 24 VAC Temperature Air Sensor for the thermostat and heating loads, Sensor Thermostat Power Sensor install a jumper across RC and RH. Figure 6: Wiring the TEC2003-3 Thermostat Controller TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions...
  • Page 5: Setup And Adjustments

    Installer Configuration Menu or to alarm condition is displayed. exit the menu (See the Installer Configuration Menu section.) • UP/DOWN arrow keys change the configuration parameters and activate a setpoint adjustment. TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions...
  • Page 6: Configuring The Thermostat Controller

    Note: Setting this parameter to 10 disables the function. Only devices using the same mesh network channel can communicate with each other. Default: 10 GET FROM Parameter not available at this time. TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions...
  • Page 7 (fan, heating, or cooling) is authorized. Also can be used to sequence the startup of multiple units in one location. Default: 10.0 sec TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions...
  • Page 8 • an Override Function enabled in the Main User Menu (when the thermostat controller is in the Unoccupied mode) • a temporary heating or cooling setpoint default: 3.0 hrs TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions...
  • Page 9: Programming The Thermostat Controller

    MENU key during normal left unattended for 45 seconds, the menu reverts to the operation. The Main User Menu contains the basic Status Display Menu. operating features of the thermostat controller. TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions...
  • Page 10 Press the UP/DOWN arrow keys to set the temperature. Press the YES Unocc CL key to store the value and advance to 80.0 ° F the next menu. TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions...
  • Page 11 3. Press the YES key to return to the Status Display The setpoint reverts to the Permanent Temperature Menu or press the NO key to return to the fan Setpoint. mode selection menu. TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions...
  • Page 12: Troubleshooting

    Duct Mount Air Temperature Sensor TE-6361M-1 Outdoor Air Temperature Sensor TE-6363-1 Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details. TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions...
  • Page 13: Technical Specifications

    The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

Table of Contents