Table 5: Selection Options for Sequence of Operation in Four-Pipe Applications
Selection
Option
(0): Cooling Only
(1): Heating Only
(2): Cooling with Reheat
(3): Heating with Reheat
(4): Cool/Heat Four-Pipe
(5): Cool/Heat Four-Pipe
and Reheat
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Control
Terminal Numbers Used (See Table 2 and Figure 5.)
Curve
On/Off Control
See Figure 16.
10: N.O. Cooling
11: N.C. Cooling
See Figure 17.
8: N.O. Heating
9: N.C. Heating
See Figure 18.
6 and 7: Reheat
10: N.O. Cooling
11: N.C. Cooling
See Figure 19.
6 and 7: Reheat
8: N.O. Heating
9: N.C. Heating
See Figure 20.
8: N.O. Heating
9: N.C. Heating
10: N.O. Cooling
11: N.C. Cooling
See Figure 21.
6 and 7: Reheat
8: N.O. Heating
9: N.C. Heating
10: N.O. Cooling
11: N.C. Cooling
Capability, Fan Control, and Occupancy Sensing Capability
Floating Control
Proportional
0 to 10 VDC Control
10: Open Cooling
10: Proportional Cooling
11: Closed Cooling
8: Open Heating
9: Proportional Heating
9: Closed Heating
6 and 7: Reheat
6 and 7: Reheat
10: Open Cooling
10: Proportional Cooling
11: Closed Cooling
6 and 7: Reheat
6 and 7: Reheat
8: Open Heating
9: Proportional Heating
9: Closed Heating
8: Open Heating
9: Proportional Heating
9: Closed Heating
10: Proportional Cooling
10: Open Cooling
11: Closed Cooling
6 and 7: Reheat
6 and 7: Reheat
8: Open Heating
9: Proportional Heating
9: Closed Heating
10: Proportional Cooling
10: Open Cooling
11: Closed Cooling