Technical Specifications; Tec20X6(H)-4 And Tec20X6H-4+Pir Series Wireless Thermostat Controllers With Dehumidification Capability, Fan Control, And Occupancy Sensing Capability (Part 1 Of 2) - Johnson Controls TEC20x6-4 Series Installation Instructions Manual

Table of Contents

Advertisement

Table 8: Accessories (Order Separately)
Code Number
Description
SEN-600-1
Remote Indoor Air Temperature Sensor
SEN-600-4
Remote Indoor Air Temperature Sensor with Occupancy Override and LED
1
Duct Mount Air Temperature Sensor
TE-6361M-1
TE-636S-1
Strap-Mount Temperature Sensor
TEC20-A-1
Replacement Antenna for TEC20 Coordinator
2
Remote Antenna for TEC20 Coordinator
TEC20-RA-1
3
DIN Rail Mount 24 VAC/DC Power Module for TEC20 Coordinator
NPB-PWR
TEC20-8X-1
120 VAC to 15 VDC Power Supply for TEC20 Coordinator
TEC20-9B-1
Replacement Battery Pack for TEC20 Coordinator
4
Cover with Occupancy Sensor
TEC-6-PIR
5
Cover with Occupancy Sensor for Hospitality Models
TEC-6H-PIR
1.
Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the
TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
2.
This antenna is used when the TEC Coordinator is installed inside a metal cabinet, or when a remote antenna is required by
physical installation.
3.
DIN Rail: Type NS35/7.5 (35 x 7.5 mm) and DIN rail end clips. Length of DIN rail depends on the number of DIN rail
mounted options.
4.
The TEC-6-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC20x6-4 Series Thermostat
Controller to provide occupancy sensing capability.
5.
TEC-6H-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC20x6H-4 Series Thermostat
Controller to provide occupancy sensing capability.

Technical Specifications

TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability (Part 1 of 2)
Power Requirements
Relay/Triac Contact Rating
Analog Output Rating
Fan Relay Output Rating
Auxiliary Output Rating
Binary Inputs
Analog Inputs
Wire Size
Recommended Transmission
Range
RF Band
Transmission Power
Temperature Range
Temperature Sensor Type
Resolution
24
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Capability, Fan Control, and Occupancy Sensing Capability
19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
On/Off and Floating Control: 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum,
3.0 A In-Rush, Class 2 or SELV
Proportional Control: 0 to 10 VDC into 2k ohm Resistance (Minimum)
19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV
Triac Output: 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush
Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3
Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
Temperature Coefficient (NTC) Thermistor Sensors
18 AWG Maximum, 22 AWG Recommended
Through Walls: 10 m (30 ft)
Line-of-Sight (Open Space): 30 m (100 ft)
Direct-Sequence Spread-Spectrum Transmission; 2.4 Ghz unlicensed band
10 mW Maximum
Backlit Display: -40.0°C/-40.0°F to 50.0°C/122.0°F in 0.5° increments
Heating Control: 4.5°C/40.0°F to 32.0°C/90.0°F in 0.5° Increments
Cooling Control: 12.0°C/54.0°F to 38.0°C/100.0°F in 0.5° Increments
Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor
±0.1C°/±0.2F°