Johnson Controls TEC20x6-4 Series Installation Instructions Manual page 18

Table of Contents

Advertisement

Table 6: Installer Configuration Menu (Part 3 of 8)
Parameter
Description and Default
Appearing
on Display
UI3
Configuration of Universal Input 3.
Default: None
MenuScro
Gives the option of having the
display continuously scroll the
parameters.
Default: on
AutoMode
Enables the Auto function (if
Option 2 is chosen in the SeqOpera
parameter) to be visible within the
MODE key menu. (The MODE key
is the key at the far left of the
thermostat controller cover.)
Default: on
C or F
Provides temperature scale options
for display.
Default: °F
%RH disp
Displays the current humidity
reading (TEC2036-2, TEC2036H-2,
TEC2056-2, and TEC2056H-2
models).
Default: off
Lockout
Selectable Lockout Levels for
limiting end user keypad interaction.
Default: 0
18
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Capability, Fan Control, and Occupancy Sensing Capability
Selection Options
(None): No function is associated with an input.
(COC/NH): Changeover Contact/Normally Heat: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact
closes when cold water is present. Valid only for two-pipe systems.
(COC/NC): Changeover Contact/Normally Cool: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact
closes when hot water is present. Valid only for two-pipe systems.
(COS): Changeover Analog Sensor: Used for hot/cold water
changeover switching. Valid only for two-pipe systems.
Note: Choose the selection option (0): Cooling Only for the
SeqOpera parameter to allow changeover to occur between
Cooling Only and Heating Only. The changeover sensor does not
operate in Cooling and Reheat, Heating and Reheat, or Cool/
Heat Four-Pipe and Reheat applications.
(SS): Supply Air Sensor Monitoring
Note: If UI3 is set to None, COC/NH, or COC/NC, then UI3 Status
is available as a point for integration and Supply Temperature is
not available as a point for integration. If UI3 is set to COS or SS,
then Supply Temperature is available as a point for integration and
UI3 Status is not available as a point for integration.
(off): The scroll is inactive.
(on): The scroll is active.
(on): The Auto function is active (Off-Auto-Heat-Cool). Provides
automatic changeover between heating and cooling.
(off): The auto function is inactive (Off-Heat-Cool).
(°C): Celsius scale
(°F): Fahrenheit scale
(on): Displays the current humidity reading in% RH.
(off): Does not display the current humidity reading.
Lockout
Level
Mode
Fan
Setting
Setting
(0)
Access
Access
(1)
Access
Access
(2)
No Access
No Access
(3)
No Access
No Access
(4)
No Access
No Access
(5)
No Access
No Access
Function
Local
Occupied
Override
Temperature
Setpoints
Access
Access
No Access
Access
Access
Access
No Access
Access
Access
No Access
No Access
No Access