Table 6: Installer Configuration Menu (Part 4 of 8)
Parameter
Description and Default
Appearing
on Display
Pipe No
Selectable number of pipes in the
system.
Default: 4.0 Pipes
CntrlTyp
Defines the control output for the
type of valves used in the
installation (TEC2026-2,
TEC2026H-2, TEC2036-2, and
TEC2036H-2 models).
Default: Floating
SeqOpera
Determines the sequence of
operation.
Default: 1
Fan Menu
Sets the Fan Mode options.
Default: 4
DHumiLCK
Locks out the dehumidification
capability (TEC2036[H]-2, and
TEC2056[H]-2 models).
Default: on
1
Sets the dehumidification setpoints
%RH set
(TEC2036[H]-2, and TEC2056[H]-2
models). This parameter can be
used only if the dehumidification
sequence is enabled.
Default: 50.0% RH
1
Sets the dehumidification hysteresis
DehuHyst
(deadband) (TEC2036[H]-2, and
TEC2056[H]-2 models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 5.0% RH
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Selection Options
(2.0 Pipes): Limits the number of sequences of operation available
from 0 to 3, and enables heat/cool operation from the same output.
(4.0 Pipes): Allows access to all sequences of operation from 0 to 5,
and enables heat/cool operation from different outputs.
(On/Off): For Normally Open (N.O.) or Normally Closed (N.C.)
24 VAC two-position valves.
(Floating): For proportional three-wire control of 24 VAC floating
valves.
(0): Cooling Only (Off-Cool). The default is Cool.
(1): Heating Only (Off-Heat). The default is Heat.
(2): Cooling and Reheat (Off-Auto*-Heat-Cool). The default is Auto.
(3): Heating and Reheat (Off-Heat). The default is Heat.
(4): Cool/Heat Four-Pipe (Off-Auto*-Heat-Cool). The default is Auto.
(5): Cool/Heat Four-Pipe and Reheat (Off-Auto*-Heat-Cool). The
default is Heat.
* Auto can be disabled with the AutoMode parameter. When Auto
is disabled, the default for (2) and (4) is Heat.
Note: Choose the selection option (0): Cooling Only when using a
changeover sensor to allow changeover to occur between Cooling
Only and Heating Only. Choose the selection option (2): Cooling
and Reheat when using a changeover sensor to allow changeover
to occur between Cooling and Reheat and Heating and Reheat.
(0): Low-Med-High: Three-speed configuration using three fan
relays (L-M-H). The default is High.
(1): Low-High: Two-speed configuration using two fan relays (L-H).
The default is High.
(2): Low-Med-High-Auto: Three-speed configuration with Auto Fan
speed mode using three fan relays (L-M-H). The default is High.
(3): Low-High-Auto: Two-speed configuration with Auto Fan speed
mode using two fan relays (L-H). The default is High.
(4): On-Auto: One-speed configuration, (H) Auto is for Fan on
demand and On is for Fan on all the time. The default is Auto.
(off): Dehumidification is locked out.
(on): Dehumidification is allowed.
Range: 30.0 to 95.0% RH
Range: 2.0 to 20.0% RH
Capability, Fan Control, and Occupancy Sensing Capability
19