13. Enter the BACnet MS/TP address through the
keypad.
14. Press Save.
15. After selecting N2 in Step 6, press Save.
16. Press the back arrow to return to the previous
screen.
17. Press N2 Address.
18. Enter the N2 address through the keypad.
19. Press Save.
Configuring the network settings for
wireless models
1.
Ensure the TEC screen is on.
2.
Press the Menu icon.
3.
Press Setup.
4.
Press Network Setup.
5.
Press FC Comm Mode and the Wireless Field Bus
appears. This setting cannot be changed.
6.
Press the back arrow to return to the previous
screen.
7.
Press BACnet Instance ID.
8.
Enter the BACnet
®
This value should be different to the other
controllers on the site.
9.
Press Save.
10. Press the back arrow to return to the previous
screen.
11. Press BACnet Address.
12. Enter the BACnet address using the keypad. This
value should be different to the other controllers
on the PAN.
13. Press Save.
14. Press the back arrow to return to the previous
screen.
15. Press PAN ID.
16. Enter the PAN ID using the keypad. This value
needs to be the same as set in the associated
ZFR182x or ZFR183x Coordinator Radio.
17. Press Save.
Once the PAN is set, the TEC attempts to
connect to the wireless network. Provided that
other devices on the PAN are in radio range,
the connection should occur within one minute.
It can then take up to 10 minutes for the WNC
gateway to display that the device is online.

Configuring the thermostat controller

Use the Menu icon on the home screen to access and
change the basic operating parameters of the thermostat
controller. During normal operation, press the Menu icon
once to access the following parameters:
• Fault Status
• Setpoints
• Schedule
• Display Settings
• Setup
14
TEC3000 Series Proportional Fan Coil Thermostats Installation Guide
instance ID using the keypad.
• Trend
• Status
• Update

Installer configuration menu

The thermostat controller comes from the factory with
default settings for all configuration parameters. The
UI menu navigation and default settings are shown in
Table 14. Before any outputs turn on, the controller must
be configured for the equipment connected. You need
to start from the home screen to perform any of the
following tasks.
Screen reset
The current screen returns to the home screen and turns
off if the current screen is not touched for 3 minutes.
Touch the screen to turn it on again. To disable the
screensaving option, press Display Settings and set
Enable Display Timeout to No.
Selecting the unit type
About this task:
There are three unit types. They are:
• Four-pipe—This unit type has both heating and cooling
coils plus a supply fan. This configuration can also be
used on configurations that are heating or cooling only.
• Two-pipe—This unit type has a single set of pipes that
can serve hot or chilled water plus a supply fan. The
Supply Temp Type allows for the connection of an
analog sensor or an aquastat to a binary input. Based
on the water temperature or aquastat state, the unit
controls heating or cooling.
• VAV—This unit type is designed for a pressure-
dependent zone damper and the supply fan
outputs are disabled. The TEC senses the supply
air temperature coming from the unit. The Supply
Temp Type setting allows for the connection of an
analog sensor or binary duct thermostat. Based on
the air temperature or duct thermostat state, the zone
damper controls for heating or cooling. The TEC does
not control the unit delivering the air. The logic needs
to be part of another controller.
By default, the thermostat controller is configured for
four-pipe fan coil mode. To change to a two-pipe or
Pressure-Dependent VAV mode, complete the following
steps:
1.
Press the Menu icon.
2.
Press Setup.
3.
Press Equipment Setup.
4.
Press General.
5.
Press Unit Type and select 2-pipe, 4-pipe, or VAV.
6.
Press Save and the back arrow to return to the
previous screen.
Note: When you select VAV, the controller
reboots in order to apply the change.