TEC2045-2
Application
IMPORTANT: The TEC2045-2 Wireless
Thermostat Controller is intended to provide an input
to equipment under normal operating conditions.
Where failure or malfunction of the thermostat
controller could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices such as supervisory or alarm systems
or safety or limit controls intended to warn of, or
protect against, failure or malfunction of the
thermostat controller.
The TEC Series Wireless Thermostat Controller
System provides wireless networked control of
Heating, Ventilating, and Air Conditioning (HVAC)
equipment on a Building Automation System (BAS)
that enables remote monitoring and programming. This
TEC Series System integrates into a supervisory
controller using BACnet® Internet Protocol (IP) or
BACnet Master-Slave/Token-Passing (MS/TP)
communications.
TEC20 Coordinators allow the supervisory controller to
communicate with multiple TEC Wireless Thermostat
Controllers. TEC2045-2 Wireless Thermostat
Controllers control two-pipe fan coils, cabinet unit
heaters, or other equipment using a proportional 0 to
10 VDC control input and one-speed fan control.
The wireless mesh network uses ZigBee® technology
to enable remote monitoring and programming and to
enhance reliability by providing redundant transmission
paths through other TEC Wireless Thermostat
Controllers, creating a resilient, self-healing mesh
network.
TEC2045-2 Wireless Thermostat Controller with Single Proportional Output and One-
Part No. 24-9890-757, Rev. —
North American Emissions Compliance
United States
This equipment has been tested and found to comply with
the limits for a Class A digital device pursuant to Part 15 of
the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when
this equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications. Operation
of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be
required to correct the interference at his/her own
expense.
RF Transmitters: Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received,
including interference that may cause undesired
operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by the
party responsible for compliance could void the user's
authority to operate the equipment.
Canada
This Class (A) digital apparatus meets all the requirements
of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (A) respecte toutes
les exigences du Règlement sur le matériel brouilleur du
Canada.
RF Transmitters: Industry Canada Statement
The term IC before the certification/registration number
only signifies that the Industry Canada technical
specifications were met.
Le terme « IC » précédant le numéro d'accréditation/
inscription signifie simplement que le produit est conforme
aux spécifications techniques d'Industry Canada.
Speed Fan Control Installation Instructions
Release 4.0
Issued March 17, 2008
1

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls TEC2045-2

  • Page 1: Installation Instructions

    Le terme « IC » précédant le numéro d'accréditation/ inscription signifie simplement que le produit est conforme aux spécifications techniques d'Industry Canada. TEC2045-2 Wireless Thermostat Controller with Single Proportional Output and One- Speed Fan Control Installation Instructions...
  • Page 2: Location Considerations

    (included) flush to the wall surface. Note: Other means of anchoring the device may be desired, depending on the wall medium. TEC2045-2 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions...
  • Page 3 5. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the cover. See Figure 5, Figure 6, Figure 7, and Table 2 for information on wiring the thermostat controllers. TEC2045-2 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions...
  • Page 4 Independent Thermostat Power Contacts • Reheat • Lighting • On/Off Actuation • Exhaust Fan Figure 6: TEC2045-2 Thermostat Controller with Separate Power Source for Auxiliary Contact TEC2045-2 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions...
  • Page 5: Setup And Adjustments

    24 VAC = Hot Water COS (Change Over Sensor) Thermostat Power Figure 7: TEC2045-2 Thermostat Controller with Same Power Source for Auxiliary Contact Setup and Adjustments • FAN key toggles between ON and AUTO for fan control. ON energizes the fan all the time and...
  • Page 6: Configuring The Thermostat Controller

    2: Cooling and Reheat See Figure 11. 6 and 7: Reheat 10: Proportional Cooling 3: Heating and Reheat See Figure 12. 6 and 7: Reheat 10: Proportional Heating TEC2045-2 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions...
  • Page 7 Heating Output Cooling Output Cooling Setpoint Heating Setpoint Deadband Device Opened Reheat Proportional Device Output Closed Temperature Increase (Increments of 1F°/0.5C°) Figure 11: Cooling with Reheat TEC2045-2 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions...
  • Page 8 * These settings disable any local override function. **When this setting is selected, the heating and/or cooling outputs are enabled only when the contact is closed. TEC2045-2 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions...
  • Page 9 Default: off C or F Provides temperature scale options (°C): Celsius scale for display. (°F): Fahrenheit scale Default: °F TEC2045-2 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions...
  • Page 10 Default: 2.0 hrs DoorTime Engages the Unoccupied mode if Range: 1.0 to 10.0 min the door stays open minimally for the time specified. Default: 2.0 min TEC2045-2 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions...
  • Page 11 UI3 is configured sensor operation. as an analog input (supply sensor or changeover sensor). Used as a diagnostic/service help, to troubleshoot and diagnose sensor operation. Default: -40°F/-40°C TEC2045-2 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions...
  • Page 12: Troubleshooting

    TE-636S-1 Strap-Mount Temperature Sensor Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details. TEC2045-2 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control...
  • Page 13: Technical Specifications

    The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

Table of Contents