Table 6: Installer Configuration Menu (Part 2 of 8)
Parameter
Description and Default
Appearing
on Display
Channel
Sets the mesh network channel the
device uses for communication.
Only devices using the same mesh
network channel can communicate
with each other. Default: 10
GET FROM
Parameter not available at this time.
BI1
Configuration of Binary Input 1.
Default: None
BI2
Configuration of Binary Input 2.
Default: None
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Selection Options
Range: 11 to 26
Note: Setting this parameter to 10 disables the function.
N/A
(None): No function is associated with an input.
(Rem NSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
(MotionNO*): Temporary occupancy request via a motion detector
input. Contact open = Unoccupied. When the contact closes, the
thermostat controller goes into the occupied mode for a specified
TOccTime. Once the TOccTime begins, the thermostat controller
remains in the occupied mode if the contact is open, until the
TOccTime expires.
(MotionNC*): Temporary occupancy request via a motion detector
input. Contact closed = Unoccupied. When the contact opens, the
thermostat controller goes into the occupied mode for a specified
TOccTime. Once the TOccTime begins, the thermostat controller
remains in the occupied mode if the contact is closed, until the
TOccTime expires.
(Window): Cancels the heating or cooling action when a window is
open. The fan operation is only affected if the Fan Menu parameter
is set to (4): On-Auto and Auto is the selected fan mode. A window
alarm appears, indicating that the window needs to be closed to
resume heating or cooling.
*These settings disable any local override function.
(None): No function is associated with an input.
(Door Dry): Door contact only has an effect if BI1 is set to
MotionNO or MotionNC. (See the BI1 parameter earlier in this
table.) The occupancy is now dictated via BI1 and BI2. Any motion
detected sets the zone to Occupied status. The zone remains
permanently in occupied mode until the door contact switch opens
momentarily. The thermostat then enters stand-by mode. If more
movements are detected, the occupied mode resumes. While the
door is opened, any movements detected by the remote PIR sensor
or the PIR accessory cover are ignored. Use a Normally Closed
contact switching device. Contact opened = Door opened,
Contact closed = Door closed.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat controller.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat controller
when the input is energized. This input can be tied into the air
conditioning unit control card, which provides an alarm should there
be a malfunction.
Capability, Fan Control, and Occupancy Sensing Capability