Configuring the TEC22x6(H)-4 and
TEC22x6H-4+PIR Series Thermostat
Controllers
The TEC22x6(H)-4 and TEC22x6H-4+PIR Series
Thermostat Controllers are shipped with default
settings for all configurable parameters. The default
settings are shown in Table 5. To reconfigure the
parameters via the thermostat, follow the steps in this
section.
1. To access the Installer Configuration Menu, press
and hold the center key for approximately
8 seconds.
Note: If the Password parameter is configured,
Password 0 appears on the thermostat controller
display indicating that the configured password is
required to proceed. Use the UP/DOWN arrow
keys to indicate the configured password, then
press the MODE key to proceed through the
Installer Configuration Menu parameters.
2. Once the Installer Configuration Menu begins,
press and release the center key to scroll through
the parameters listed in Table 5.
3. When the desired parameter is displayed, use the
UP/DOWN arrow keys to choose the desired
selection option.
4. Press and release the center key to continue
scrolling through the parameters.
Note: Pressing the FAN key during configuration
restarts the list of displayed parameters at the first
parameter listed in Table 5.
When the thermostat is in the Installer Configuration
Menu and left unattended for approximately 8 seconds,
the thermostat reverts to the Status Display Menu.
For additional information on commissioning and
configuring thermostat controllers, adding thermostat
controllers to a Network Automation Engine (NAE),
thermostat controller mapping, and remote thermostat
controller commanding, refer to TEC22x6(H)-4 and
TEC22x6H-4+PIR L
W
ON
Controllers with Dehumidification Capability, Fan
Control, and Occupancy Sensing Capability Technical
Bulletin (LIT-12011610).
TEC22x6(H)-4 and TEC22x6H-4+PIR Series L
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
® Network Thermostat
ORKS
Configuring the Thermostat Controller's
Neuron® Identification
Press and hold the UP/DOWN arrow keys
simultaneously for 5 seconds to broadcast the
thermostat controller's Neuron Identification on the
L
W
network.
ON
ORKS
If the cover is removed, you can see a green LED
under the LON board flash when the thermostat
broadcasts the Neuron ID. The Neuron ID is on a label
on the Echelon® chip.
You cannot send the Neuron ID while in the Installer
Configuration menu.

Configuring Inputs BI1, BI2, and UI3

When BI1 and BI2 are configured for an alarm
condition, an alarm condition is displayed locally when
the input is closed. An alarm message is included on
the scrolling Status Display Menu and when the
message is displayed, the backlight momentarily
lights up.
The UI3 input provides changeover of hot/cold water
switching or supply air temperature monitoring at the
thermostat.
Each input can be configured to the Selection Options
included in Table 5.
Configuring the Sequence of Operation
(SeqOpera)
Choose the appropriate sequence of operation. The
modes presented are user-dependent on the sequence
of operation selected. For 2-pipe applications using a
COS, choose 0 = Cooling only. Changeover occurs
between Cooling only and Heating only. For example
sequences of operation, see Figure 15 through
Figure 20.
W
® Network Thermostat Controllers with
ON
ORKS
11