Tec2645-4 Thermostat Controller - Johnson Controls TEC2645-4 Technical Bulletin

Network temperature and humidity controllers
Table of Contents

Advertisement

TEC2645-4 Thermostat Controller

Table 4: TEC2645-4 MS/TP Bus Objects (Part 1 of 4)
Point Name
1, 2
Room Temp
3
Room Temp Override
3, 4
Outdoor Temperature
5
Supply Temperature
3
AUX Command
Sequence of Operation
3
System Mode
3
Fan Mode
3
Occupancy Command
3
Keypad Lockout
5
PI Heating Demand
5
PI Cooling Demand
5
AUX (BO5) Status
2, 5
Fan Status
5, 6
BI1 Status
5, 6
BI2 Status
5, 6
UI3 Status
5
Local Motion
5
Effective Occupancy
5
Window Alarm
18
TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
Thermostat Point
(Type/Address)
AV 7
BV 8
AV 9
AI 12
BV 14
3
MSV 15
MSV 16
MSV 17
MSV 18
MSV 19
AV 21
AV 22
BI 25
MSV 28
BI 29
BI 30
BI 31
BI 32
MSV 33
BI 35
Range
-40.0°F/-40.0°C to
122.0°F/50.0°C
0 = Normal
1 = Override
-40.0°F/-40.0°C to
122.0°F/50.0°C
-40.0°F/-40.0°C to
122.0°F/50.0°C
0 = Off
1 = On
0 = Cooling Only
1 = Heating Only
2 = Cooling and Reheat
3 = Heating and Reheat
1 = Off
2 = Auto
3 = Cool
4 = Heat
1 = On
2 = Auto
1 = Resume Schedule
2 = Occupied
3 = Unoccupied
4 = Temporary Occupied
1 = Level 0
2 = Level 1
3 = Level 2
4 = Level 3
5 = Level 4
6 = Level 5
0 to 100%
0 to 100%
0 = Off
1 = On
1 = Off
4 = High
0 = Deactivated
1 = Activated
0 = Deactivated
1 = Activated
0 = Deactivated
1 = Activated
0 = Deactivated
1 = Activated
1 = Occupied
2 = Unoccupied
3 = Temporary Occupied
4 = Stand-by
0 = Off
1 = On