Thermistor Or Related Abnormality (Indoor Unit) - Daikin FTXG20LV1BW Service Manual

Inverter pair wall mounted type l-series
Hide thumbs Also See for FTXG20LV1BW:
Table of Contents

Advertisement

Troubleshooting
4.5

Thermistor or Related Abnormality (Indoor Unit)

C4 , C9
Error Code
Method of Error
The temperatures detected by the thermistors determine thermistor errors.
Detection
Error Decision
The thermistor input is 4.96 V and more or 0.04 V and less during compressor operation.
Conditions
Supposed
Causes
Troubleshooting
Check No.01
Refer to P.93
Check the connection of
connectors.
C4
C9
63
Disconnection of connector
Thermistor corresponding to the error code is defective.
Defective indoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Normal?
YES
Check No. 01
Check the thermistor resistance
value.
Normal?
YES
: Indoor heat exchanger thermistor
: Room temperature thermistor
NO
NO
SiBE041401E
Correct the connection.
Replace the thermistor.
Replace the indoor unit PCB.
(R15717)