Temperature Controller As Temperature Limiter (Maximum Limit); Temperature Controller - Viessmann VITOSOL 100-F SV Technical Manual

Table of Contents

Advertisement

Solar control units
(cont.)
0
7 2
1 3
Specification
Connection
IP rating

Temperature controller as temperature limiter (maximum limit)

Part no. Z001 887
With stainless steel sensor well R½ x 200 mm.
With setting scale in the casing.
0
7 2
1 3

Temperature controller

Part no. 7151 989
Suitable for:
■ Vitocell 100-B
■ Vitocell 100-V
■ Vitocell 340-M
■ Vitocell 360-M
■ With a thermostatically controlled system.
■ With selector on the outside of the casing.
■ Without sensor well
The sensor well is part of the standard delivery of Viessmann DHW
cylinders.
■ With top-hat rail to be mounted to the DHW cylinder or the wall.
0
7 2
1 3
VITOSOL
3-core lead with a cross-section of
2
1.5 mm
IP 41 to EN 60529
Switching point
Switching differential
Breaking capacity
Switching function
DIN reg. no.
Specification
Connection
Setting range
Switching differential
Breaking capacity
Switching function
DIN reg. no.
Specification
Connection
IP rating
Setting range
Switching differential
Breaking capacity
Switching function
DIN reg. no.
120 (110, 100, 95) °C
max. 11 K
6(1.5 ) A, 250 V~
with rising temperature from 2 to
3
3
2
1
DIN STB 1169
3-core lead with a cross-section of
2
1.5 mm
30 to 80 °C
max. 11 K
6(1.5) A 250 V~
with rising temperature from 2 to
3
3
2
1
DIN TR 1168
3-core lead with a cross-section of
2
1.5 mm
IP 41 to EN 60529
30 to 60 °C,
adjustable up to 110 °C
max. 11 K
6(1.5) A 250 V~
with rising temperature from 2 to
3
3
2
1
DIN TR 1168