Vertical Installation On Pitched Roofs, Installation On Supports Or Horizontal Installation; Horizontal Installation On Pitched Roofs And On Walls - Viessmann VITOSOL 100-F SV Technical Manual

Table of Contents

Advertisement

Information regarding design and operation
Note
2
Max. 15 m
absorber area can be connected in series to form a single
array.

Vertical installation on pitched roofs, installation on supports or horizontal installation

Connection to the left
A
A Collector temperature sensor in the flow line
Connection to the right
A
A Collector temperature sensor in the flow line

Horizontal installation on pitched roofs and on walls

Single sided connection from below (preferred version)
1 collector array
A
With this connection, the "Relay kick" function on the Vitosolic 200
must be enabled (see chapter "Functions" in the "Solar control units"
section).
A Collector temperature sensor in the flow line
With this installation, the following minimum flow rates in the (partial)
collector array must be ensured:
2
2
1.26 m
110 l/(hm
)
1.51 m
2
90 l/(hm
2
)
VITOSOL
15m²
(cont.)
15m²
A Collector temperature sensor in the flow line
3.03 m
2
45 l/(hm
2
)
4.54 m
2
30 l/(hm
2
)
2
2
≥6.06 m
25 l/(hm
)
A
VIESMANN
143