Worcester CDi Combi N.G Service Booklet page 70

Floor mounted and wall hung rsf gas fired condensing boilers
Table of Contents

Advertisement

TROUBLESHOOTING - TD 200
Complaint
Cause
Required temperature
Thermostat valve(s) in the control room set
not reached
to low
Flow temperature controller on the heating
appliance set too low
Air lock in the heating system
Required room
Installation location of the TD 200 not
temperature is greatly
suitable, e.g. outer wall, proximity to
exceeded
window, draught, ...
Excessive room
Temporary effect of heat from other
temperature
sources on the room, e.g. from sunshine,
fluctuations
room lighting, TV, fireplace etc.
Temperature rise
Time of day incorrectly set
instead of fall
Room temperature
Building has high degree of heat storage
too high in Economy
mode
Incorrect or no
Bus connection defective for the devices
control
using the bus
Only Automatic mode
Operating switch defective
can be set
Tab. 37
70
Supplied By www.heating spares.co Tel. 0161 620 6677
Remedy
Fully open the thermostat valve(s)
or replace them with manual valve(s).
Set flow temperature controller higher.
Vent radiator and heating system.
Choose a better installation location for TD 200
(see Installation Instructions of the TD 200).
Choose a better installation location for TD 200
(see Installation Instructions of the TD 200).
Check setting.
Select Economy mode earlier.
Check the bus connection, if necessary, rectify
according to the connection diagram.
Replace the TD200
8 716 115 748 (2009/09)