Worcester CDi Combi N.G Service Booklet page 59

Floor mounted and wall hung rsf gas fired condensing boilers
Table of Contents

Advertisement

Information displayed (
and 4 in fig.16)
Text
Fault 11
System configuration: new BUS
device
New ISM detected. Power up all
ISMs simultaneously and start
automatic system configuration.
Fault 12
System configuration: BUS
device missing
ISM1 not detected. Check
connection.
Fault 13
System configuration: BUS
device changed or replaced
Check system configuration for
DHW or start automatic system
configuration.
Fault 13
System configuration: BUS
device changed or replaced
Check system configuration for
heating circuit!
Fault 15
Outside temperature sensor not
connected
Outside temperature is not
available.
Fault 19
Unable to save parameter
settings
Fault 20
System configuration: invalid
Fault 29
Unable to save parameter
settings
Fault 30
Mixer temperature sensor faulty
Fault 33
Temperature sensors incorrectly
connected
Fault 40
Temperature sensor T1 on
collector group 1 faulty
Fault 41
Temperature sensor T2 at
bottom of solar cylinder faulty
Tab. 30
8 716 115 748 (2009/09)
Supplied By www.heating spares.co Tel. 0161 620 6677
Pos. 1, 3
Code Cause
131
New ISM detected.
132
170
HLC has tripped or is faulty.
171
ISM1 no longer detected despite
having been configured.
157
BUS device changed or replaced.
158
159
30
Outside temperature sensor not
recognised.
202
BUS device is configured but not
available at present.
193
Invalid coding in remote control for
the heating circuit.
202
BUS device is configured but not
available at present.
7
Mixer temperature sensor (MF)
connected to IPM faulty.
22
A temperature sensor is connected
to the IUM.
101
Short circuit on the sensor lead
(T
).
1
102
Break in the sensor lead (T
103
Short circuit on the sensor lead
(T
).
2
104
Break in the sensor lead (T
TROUBLESHOOTING - FW 100
Remedy
Power up all ISMs simultaneously and
start automatic system configuration.
Check HLC.
Check solar parameter T2.
Is thermal disinfection active?
Check connection.
Check system configuration for
domestic hot water system or start
automatic system configuration.
Check system configuration for heating
circuit
Check outside temperature sensor and
remedy interruption, if necessary.
Check system layout, check system
configuration, modify if necessary and
set parameter again.
In combination with FW 100 only
coding 1 is possible in the remote
control.
Check system layout, check system
configuration, modify if necessary and
reset parameters on remote control.
Check mixer temperature sensor (MF)
and replace if necessary.
Remove the temperature sensor and
insert a coding plug if necessary.
Check temperature sensor (T
replace if necessary.
).
1
Check temperature sensor (T
replace if necessary.
).
2
) and
1
) and
2
59