F7
and RESET button and fault indicator LED are flashing.
Although appliance switches off, flame still detected
Check
1.
Electrode(s) dirty or defective?
B Switch OFF the appliance.
B Remove electrode assembly and
bracket and check for wear,
deposits and mechanical damage.
2.
Problem with flue?
B Check CO
level in combustion air
2
in the flue
(with outer casing fitted).
Is CO
level above 0.2%?
2
3.
The PCB is damaged.
Tab. 27 F7 Error codes
8 716 115 748 (2009/09)
Supplied By www.heating spares.co Tel. 0161 620 6677
Action
yes:
B Replace electrode assembly.
B Switch ON the appliance.
B Press the reset button for 3 seconds and release it.
After releasing the appliance re-starts.
F7? go to 2
no:
B Refit electrode assembly.
B Switch ON the appliance.
B Press the reset button for 3 seconds and release it.
After releasing the appliance re-starts.
F7 go to 2
yes:
There are flue gases in the combustion air.
B Check flue and repair or replace if necessary.
F7? go to 3
no:
go to 3
B Make a note of the altered service settings.
B Switch OFF the appliance.
B Disconnect the boiler power connection.
B Change PCB control board.
B Reconnect the appliance power connection.
B Switch ON the appliance.
B Restore service settings previously noted down.
RECTIFYING FAULTS