RECTIFYING FAULTS
A8
and fault indicator LED are flashing.
Bus communication to the programmer interrupted (set value not received)
Check
5
Has the bus module been replaced
6
The PCB control board is faulty
Tab. 17 A8 Error codes
34
Supplied By www.heating spares.co Tel. 0161 620 6677
Action
yes:
A8? go to 6
no:
B Switch off appliance
B Disconnect electrical power
B Replace bus module
B Reconnect appliance power
B Switch on appliance
A8? go to 5
B Reconnect electrical power
B Switch on appliance
B Make a note of the service function settings
B Switch off appliance
B Disconnect electrical power
B Change PCB control board
B Reconnect electrical power
B Switch on appliance
B Restore service settings noted previously