Worcester CDi Combi N.G Service Booklet page 37

Floor mounted and wall hung rsf gas fired condensing boilers
Table of Contents

Advertisement

CC
and fault indicator LED are flashing.
Outside temperature sensor fault (open or short circuit)
Check
1.
B Power OFF the appliance.
B Disconnect the boiler mains
connection.
Are the outside temperature sen-
sors connected to A and F on the
printed circuit board.
2.
B Power off the appliance.
At the outside temperature sensor
cable connection, measure the
resistance of the outside
temperature sensor.
Does the value match that in table
44?
3.
B Power OFF the appliance.
B Disconnect the boiler mains
connection.
B Disconnect the outside
temperature sensors at connec-
tors A and F on the PCB.
Check for continuity, is there
continuity.
4.
The PCB control board is damaged.
Tab. 20 CC Error codes
8 716 115 748 (2009/09)
Supplied By www.heating spares.co Tel. 0161 620 6677
Action
yes
go to 2
no
B Connect the outside temperature sensors correctly
to A and F on the PCB.
B Reconnect the boiler electrical mains
B Power ON the appliance
CC? go to 2
yes
go to 3
no
B Replace the outside temperature sensors.
B Power ON the appliance
CC? go to 3
yes
CC? go to 4
no
B Replace the cable.
B Reconnect the boiler electrical mains
connection.
B Power ON the appliance.
CC? go to 4
B Reconnect the boiler electrical mains connection.
B Power ON the appliance.
B Make a note of the altered service function settings.
B Power OFF the appliance.
B Disconnect the boiler electrical connection.
B Change the control board PCB.
B Reconnect the boiler electrical connection.
B Turn ON the appliance.
B Restore service settings previously noted.
RECTIFYING FAULTS
37