Worcester CDi Combi N.G Service Booklet page 35

Floor mounted and wall hung rsf gas fired condensing boilers
Table of Contents

Advertisement

b1
and fault indicator LED are flashing
Code plug not detected.
Check
1.
B Select in the second service level
the service function 8.b (Code
plug).
B Compare number displayed with
that shown in Appendix (only
digits no. 7 up to 10 of order no.).
No number or incorrect number
displayed.
B Exit the service function.
2.
Code plug loose, incorrect or
defective.
3.
The PCB is damaged.
Tab. 18 b1 Error codes
8 716 115 748 (2009/09)
Supplied By www.heating spares.co Tel. 0161 620 6677
Action
yes:
go to 2
no:
go to 3
B Switch OFF the appliance.
B Fit code plug (correctly), making sure code number
is correct (see Appendix).
B Switch ON the appliance.
b1? go to 3
B Make a note of the altered service function settings
(see table 6 on page 18) in order to keep the
altered values.
B Switch OFF the appliance.
B Disconnect the boiler power connection.
B Change PCB control board.
B Reconnect the appliance power connection.
B Switch ON the appliance.
B Restore service settings previously noted down.
RECTIFYING FAULTS