Worcester CDi Combi N.G Service Booklet page 40

Floor mounted and wall hung rsf gas fired condensing boilers
Table of Contents

Advertisement

RECTIFYING FAULTS
E2
and fault indicator LED are flashing.
Flow temperature NTC sensor defective.
Check
1.
B Check if the flow temperature
NTC sensor connector is
corroded, damaged or dirty.
2.
B Switch OFF the appliance.
B Disconnect the boiler power
connection.
B Unplug 20-pin connector from
PCB.
B Check resistance from
connections 8 to 9 on the cable
side. Does the value match the
ones described in table 38,
page 71?
3.
B Un-plug NTC sensor from cable.
B Check resistance of NTC sensor.
Does the value match the ones
described in table 38, page 71?
B Reconnect the appliance power
connection.
Tab. 23 E2 Error codes
40
Supplied By www.heating spares.co Tel. 0161 620 6677
Action
yes:
B Change relative parts.
E2? go to 2
no:
go to 2
yes:
B Reconnect the boiler electrical connection.
B Switch ON the appliance.
B Make a note of the altered service function settings
(see table 6 on page 18) in order to keep the altered
values.
B Switch OFF the appliance.
B Disconnect the boiler power connection.
B Change PCB control board.
B Reconnect the appliance power connection.
B Switch ON the appliance.
B Restore service settings previously noted down.
no:
go to 3
yes:
B Switch OFF the appliance.
B Disconnect the boiler power connection.
B Change the 20-pin connector lead assembly.
B Reconnect the boiler electrical connection.
B Switch ON the appliance.
no:
B Change NTC sensor.
8 716 115 748 (2009/09)